Energy Cable

STANDARD: BS 5467

VOLTAGE RATING: 1900/3300V (Um 3600V)

APPLICATION: Industrial and mains distribution. Can be laid direct in the ground, or in ducts, clipped to surface, on trays or in free air. May be embedded in concrete.

CONSTRUCTION: Single or Three core cables. Stranded plain copper conductors, XLPE insulated, cores laid up, extruded PVC bedding, galvanised steel wire armoured (Aluminium wires for single cores) and PVC sheathed.

CORE COLOURS:
Single core: Brown.
Three core: Brown, Black and Grey.

SHEATH COLOUR: Black

MINIMUM BENDING RADIUS: 6D circular conductors, 8D Shaped conductors.

MAXIMUM CONDUCTOR TEMPERATURE: 90°C
Note: Where a conductor operates at a temperature exceeding 70°C it shall be ascertained that the equipment connected to the conductor is suitable for the conductor operating temperature (see regulation 512-02 of BS7671, the 16th Edition of IEE Wiring Regulations)

CURRENT RATING: Refer to ERA 69-30 Pt. V or “A Closer Look at Cable”

Reduced Flame Propagation designs and OHLS® sheathed cables to BS 6724 are also available to order.

694AW33XLH_table